Problem 105-7
Source: Problem created by the website author.
A three-phase, wye-connected, 25 kVA, 60 Hz synchronous generator, operating
with a line terminal voltage of 440 V, has an
armature resistance of 0.4 Ω / phase and a synchronous reactance of 1.9 Ω / phase.
Assume the generator is operating at rated load and PF = 0.85 lagging.
Find:
a) the nominal current;
b) the real power delivered by the generator to the load;
c) the torque angle, δ;
d) the generator voltage regulation.
Solução do Problema 105-7
Since we know the power factor of the load (FP = 0.85), we can calculate the real power, that is: