band brasil
band USA
band espanha







exploded engine
motor explodido
Figure 108-01

campo giratotrio
campo giratotrio
campo giratotrio
campo giratotrio
campo giratotrio
campo giratotrio
campo giratotrio
campo giratotrio
Figure 108-02
fórmula campo rotativo
fórmula campo rotativo horário
fórmula campo rotativo anti-horário
fórmula campo resultante



    Analyzing for ω t = 45° we obtain:

    Bh   =   (0.5)(√2/2) Bmax   ĵ   -   (0.5) (√2/2) Bmax   î

    Bah   =   (0.5)(√2/2) Bmax   ĵ   +   (0.5) (√2/2) Bmax   î

    So, adding the fields together we get:
    BS   =   Bh   +   Bah   =   √2/2 Bmax   ĵ   =   0.707 Bmax   ĵ

    Conclusion:With this analysis we verified that the resulting field, for any angle analyzed, will always be on the vertical axis or is null, represented by the phasor ĵ, as was stated previously.


    The forward and backward magnetic fields of the motor each contribute a component of the total stator voltage and, in a certain sense, are in series with each other. Since both magnetic fields are present, the rotating magnetic field progressive rotor (which has a high effective rotor resistance R2 / s) will limit the flow of the stator current in the motor (which produces the progressive and retrograde fields). As the current that feeds the stator's retrograde magnetic field is limited at a low value and as the rotor's retrograde magnetic field makes a very large angle with respect to the stator's retrograde magnetic field, the torque due to retrograde magnetic fields will be very small when close to the synchronous speed. We must pay attention to the fact that when we supply the motor with a single-phase voltage, the rotor will remain stationary, that is, it will not move, as was evident in the previous considerations the torque to which the rotor is subjected is equal to zero. However, by any means, if we provide an initial spin to the rotor this will cause the magnetic fields to progressive and retrograde are of different intensities causing the emergence of a torque non-zero. This allows the engine to accelerate until it reaches its working speed.

    This is mainly due to the progressive wave of flux in the air gap increases and the back wave decreases when the rotor is placed in movement. When the motor is running at low slip, the reflected effect of rotor resistance on the progressive field, 0.5 R2 / s, is significantly greater than the value observed with the rotor stopped, while that the effect on the field retrograde, 0.5 R2 / (2 -s), is smaller. Therefore, the impedance of the progressive field is greater than that of the stationary rotor, while that of the retrograde field is smaller. So, the counter-electromotive force of the progressive field is greater than that of the stopped rotor, unlike the force counter electromotive of the retrograde field, which is smaller. In other words, the progressive wave of flow increases, while the retrograde wave of flow decreases.

    In addition to the average net conjugate, there are pulsations of conjugate with twice the stator frequency. These torque pulsations occur when magnetic fields progressive and retrograde intersect twice each cycle. Thus, for a motor fed from a network whose frequency is 50 Hz, it will present a pulsation of 100 Hz. And in the case of the network 60 Hz the pulse will be 120 Hz. The Figure 108-03 shows this situation. We use power as a reference because we know that there is a direct relationship between power and torque. Although these pulsations do not produce average torque, they do intensify the engine vibration, what makes single phase induction motors noisier than three-phase motors of the same size. There is no way to eliminate these pulsations, because in a single-phase circuit the instantaneous power it always occurs in pulses.

potencia pulsante
Figura 108-03

        2.1   Slip Calculation

    Assume that the motor rotor is rotating in the direction of the field, which in turn rotates progressively (counterclockwise) at a speed n (rpm). Let's represent synchronous speed as nS. So the slip sp for the progressive field is given by

fórmula escorregamento
    eq. 108-01

    Now suppose that the engine rotor rotates in a counterclockwise direction. Then, the slip sr for the retrograde field with respect to the forward field is given by

fórmula escorregamento
    eq. 108-02

    Therefore, algebraically developing the above equation, the slip sr for the retrograde field is given by

fórmula escorregamento
    eq. 108-03

    3.   Crossed Field Theory

    It is a theory between the voltages and currents that the stator's stationary magnetic field can induce in the stator's bars rotor when it is in motion.

    Consider a single-phase induction motor with a rotor that has been brought to the operating speed through some external method. Voltages are induced in the bars of this rotor, with the voltage peak occurring in windings that pass directly below the windings of the stator. In turn, these voltages produce a current flow in the rotor which, Due to its high reactance, it lags behind the voltage by almost 90°. As the rotor is rotating close to synchronous speed, this time interval of 90° in the current produces an angular displacement of almost 90° between the voltage plane rotor peak and the peak current plane.

    The rotor magnetic field is smaller than the stator magnetic field due to losses in the rotor, but they differ from each other by approximately 90° both in space as in time. If these two magnetic fields are added together different instants, we will see that the total magnetic field of the motor is rotating counterclockwise. With a magnetic field present in the motor, the induction motor will develop a net torque resulting in the of movement and this torque will keep the rotor rotating.

    If the engine rotor had initially been turned clockwise, then the resulting torque would be clockwise and again keep the rotor turning.


    4.   Engine Equivalent Circuit Analysis

        Single-Phase Induction

    The double rotating field theory is fundamental to understanding the operation of single-phase induction motors. When the stator is powered by a single-phase source, it actually creates two rotating magnetic waves of equal magnitude, but which rotate in opposite directions. These waves are crucial because one of them interacts with the rotor to produce the torque necessary for engine operation.The other wave, rotating in the opposite direction, does not contribute to torque and can even harm engine efficiency. Therefore, engineers and engine designers look for ways to minimize the effects of this contrary wave to improve engine performance. The analysis of this theory allows a more accurate assessment of the engine's starting and operating characteristics, as well as its efficiency and power factor.


        4.1   Circuit Analysis with Engine Stopped

    The best way to start analyzing a single-phase induction motor is examining the engine when it is stopped. At this point, the engine can be idealized as a single-phase transformer operating with its secondary circuit in short circuit. Thus, its equivalent circuit is that of a transformer. This circuit equivalent is shown in Figure 108-04.

circuito equivalente MI monofásico
Figure 108-04

    In this model the variables involved are:

  • R1 - stator winding resistance.
  • X1 - leakage reactance of the stator winding.
  • Xm - magnetization reactance.
  • R2 - rotor resistance referenced to the stator.
  • X2 - rotor leakage reactance referenced to the stator.
  • V - single-phase stator supply voltage.
  • E - voltage induced in the stator winding by air (or air gap voltage).

    It is interesting to highlight that the voltage E is produced by the stationary pulsating flow promoted by the combination of stator and rotor currents. Note that we are assuming the rotor is stopped. The voltage E produced is defined by eq. 108-04.

fórmula tensão induzida
    eq. 108-04
    where Φmax is the air gap flux.

    Analyzing the behavior of electric motors when stopped is essential for understanding how they work and for carrying out accurate diagnoses. In the case of a stopped motor, the pulsating magnetic flux in the air gap can, in fact, be divided into two rotating fields of equal magnitude but in opposite directions. This division results in two components that interact with the rotor circuit, causing both resistive and reactive voltage drops. Understanding this interaction is crucial, as it allows the rotor equivalent circuit to be divided into two parts. that reflect the effects of each magnetic field. This division is a direct application of rotating field theory, which is a pillar in the analysis of electrical machines, especially those that operate with alternating current. Furthermore, the air gap concept is essential for engine design and analysis, as it is the space where engine magnetic interaction between the stator and rotor, being a critical factor for the efficiency of the motor. It is possible to divide the rotor equivalent circuit into two sections, each corresponding to the effects of one of the magnetic fields. The equivalent circuit of the motor, including separation of effects due to progressive magnetic fields and retrograde is shown in Figure 108-05. Keep in mind that, considering the engine stopped, the slip value reduces to s = 1.

circuito equivalente MI monofásico parado
Figure 108-05

    In this way, the two halves, in the stationary rotor condition, have the same slip with respect to each rotating field.



        4.2   Circuit Analysis with Motor in Motion

    The effective rotor resistance in an induction motor is a crucial factor that influences the motor's performance, especially in relation to the relative movement between the rotor and stator magnetic fields. The progressive magnetic field, which rotates in the same direction as the rotor rotation, and the retrograde magnetic field, which rotates in the opposite direction, contribute in a different for the rotor resistance. When the motor is running, the effective resistance of the rotor to the field progressive field is different from that for the retrograde field due to the slip variation, which is the difference between the speed of the rotating magnetic field and the actual speed of the rotor. This phenomenon is fundamental to understanding the dynamic behavior of induction motors and for the development of speed and torque control methods more efficient.

    For the progressive magnetic field, the difference per unit between the rotor speed and the magnetic field speed is the slip s, being the slip defined in the same way as in the three-phase induction motor. Therefore, the rotor resistance in the circuit part associated with the progressive magnetic field is 0.5 R2 /s.

    The progressive magnetic field rotates at speed nsync and the magnetic field retrograde rotates at speed - nsync. Therefore, the total difference in speed per unit (based on nsync) between the progressive and retrograde magnetic fields is 2. Since the rotor is rotating at a speed s less than the magnetic field progressive, the total difference in speed per unit between the rotor and the retrograde magnetic field is 2 - s (see this result in eq. 108-03). Therefore, the effective resistance of the rotor in the circuit part associated with the retrograde magnetic field is 0.5 R2 / (2 - s).

    See the final equivalent circuit of the moving single-phase induction motor in Figure 108-06.

circuito equivalente MI monofásico
Figure 108-06

        4.3   Mathematical Analysis of the Engine

            Single-Phase Induction

    Power and torque relationships in electric motors are fundamental to understanding the performance and efficiency of these machines. In single-phase motors, these relationships are also applicable, considering the progressive and retrograde components of the magnetic field. The net power of a single-phase motor is the difference between the powers associated with each of these fields, while the torque net is the difference between the conjugates they produce. This principle is essential for engine design and analysis single-phase. In Figure 108-07 we see a diagram of torque versus speed.

single phase induction motor torque graph
Figure 108-07

    To make the calculation of the motor input current simpler, it is customary to define the impedances ZP and ZR, where ZP is a single impedance that is equivalent to all impedance elements of the progressive magnetic field and ZR is a single impedance that is equivalent to all impedance elements of the retrograde magnetic field. This representation is shown in Figure 108-07a.

circuito equivalente MI monofásico
Figure 108-07a

    This way, simply by looking at the circuit shown in Figure 108-07a it is possible to determine the values ​​of ZP and ZR, as it is enough to verify that it is the calculation of the equivalent impedance represented by the elements which are connected in series and parallel. Thus, using eq. 108-05 and eq. 108-06 we will find the impedance values progressive and retrograde.


fórmula impedancia progressiva
    eq. 108-05
fórmula impedancia retrógrada
    eq. 108-06

    Note carefully that after the numerical calculation of the values ​​of ZP and ZR, looking at these equations in rectangular form, we verify that there will be a real value added to an imaginary value. In ZP, the real part represents the progressive electrical resistance, RP , while the imaginary part represents the progressive electrical reactance, XP. Obviously, the same is true when we analyze the retrograde impedance. In ZR, the real part represents the retrograde electrical resistance, RR , while the imaginary part represents the retrograde electrical reactance, XR. These values ​​represent the Thévenin equivalent of the circuit. So, it is possible to write:

fórmula impedancia progressiva
    eq. 108-6a
fórmula impedancia retrógrada
    eq. 108-6b

    In Figure 108-08 we can see how we transform the circuit to obtain RP and XP. Obviously, the same is true when we analyze the retrograde impedance.

circuito equivalente MI monofásico
Figure 108-08

    To complete this analysis, using eq. 108-05 and carrying out the operations indicated in the equation, we arrive at a final result where we obtain the real part and the imaginary part of ZP. Taking into account that in general, Xm >> X2 and, therefore, we can write Xm + X2 ≈ Xm getting the results shown in equations eq. 108-7a and eq. 108-7b.

fórmula resistencia progressiva
    eq. 108-7a
fórmula reatancia progressiva
    eq. 108-7b

    These equations are valid for the progressive field. Doing the same for the retrograde field, starting from eq. 108-06 and carrying out the appropriate operations and simplifications, we arrive at the equations eq. 108-8a and eq. 108-8b.

fórmula resistencia regressiva
    eq. 108-8a
fórmula reatancia regressiva
    eq. 108-8b
    Important Note

    "Note that when using these equations there is no need to work with complex numbers.   There is a pdf available showing how we arrived at these equations. In addition, the results obtained with these equations are compared to those results of the example 9-1 from the book by Chapman, page 595,   5th edition.   If the reader is interested in read the pdf,   enough   Click here"


        4.4   Power in the Air Gap of a Single-Phase Motor

    After understanding the theoretical part involved in a single-phase induction motor, we can prepare a study to determine the various engine parameters.

    Let's start by determining the motor input current, represented by I1. Note that eq. 108-09 is obtained from the circuit shown in Figure 108-07a.

corrente no motor
    eq. 108-09

    Note that the denominator of eq. 108-09 is the total impedance of the motor. In this way, we can write the eq. 108-09a.

impedância total do motor
    eq. 108-09a

    It is important to note that the progressive air gap power of a single-phase induction motor is the power consumed by RP, given that the progressive resistor RP is the only resistor present in the progressive impedance ZP. Similarly, the engine's air gap retrograde power is the power consumed by RR. Thus, the air gap power of the engine can be found by calculating the difference between the power consumed by RP and the power consumed by RR. To maintain a nomenclature compatible with what was studied in three-phase induction motors, we will call the air gap power Pgap. Thus, the progressive power in the air gap will be represented by PPgap and the regressive power in the air gap as PRgap. So, we can write:

potencia no entreferro
    eq. 108-10

    This equation represents the value of the power developed by the rotor to produce a torque necessary to maintain the rotor rotation. This difference between the quantities PPgap and PRgap is due to the fact that the progressive and retrograde fields act in opposite directions and, as a result, they subtract each other. Thus, we can determine how much of this power will be transformed into mechanical power using eq. 108-27 (see item 4.7). Note carefully that Pgap   NO represents losses in the motor copper due to the progressive and retrograde field. These losses are provided by eq. 108-21 (see item 4.6).

    And the progressive power in the air gap is given by:

potencia progressiva no entreferro
    eq. 108-11

    And the retrograde power in the air gap is given by:

potencia retrógrada no entreferro
    eq. 108-12

    Replacing the respective values ​​in eq.108-10 with eq. 108-11 and eq. 108-12, we obtain:

potencia no entreferro
    eq. 108-13
    Important Note

    "Attention must be paid to eq. 108-10, as this equation expresses the power that will be transformed into power "mechanics" for the rotor. That is, This power will be directly related to the torque induced in the engine rotor, a torque that is essential to keep the engine moving. It is worth noting that, in technical literature, the symbols used in equations are fundamental for the correct understanding of mathematical concepts. The choice between adding or subtracting quantities can significantly change the meaning and result of an equation. Like this, Many technical literatures present this equation, using the same symbology, however, adding the two quantities instead of subtracting them. In reality, this sum refers to the electrical losses in the copper winding of the rotor."


    Therefore, the reader should be aware when the author states that copper losses are the sum of losses in the progressive field with that of the retrograde field. In this case, he is referring to "electrical" losses and not "mechanical power". Therefore, it is essential that the reader is aware of these nuances to avoid confusion and ensure the accuracy of calculations related to engine performance."

        4.5  Calculation of Torque in a Single-Phase Motor

    When we studied the three-phase induction motor we saw that the torque induced in the rotor was given by eq. 107-32, repeated below for greater clarity.

equação torque
    eq. 107-32

    Note that we use the synchronous speed in rad/s according to the frequency of the network that powers the motor, as remember that the progressive and retrograde fields rotate at this speed. It is also worth remembering the relationship between the machine's synchronous speed, ωsync, the number of machine poles, P, and the network frequency, f, given by eq 108-14.

relação entre velocidade e frequência
    eq. 108-14

    Since the two fields, progressive and retrograde, are rotating in opposite directions, the torque produced by the two fields are opposite. Then, the resulting torque developed is the difference between them, according to eq. 108-15.

torque e potencia
    eq. 108-15

    Using eq. 108-13, it is also possible to express torque as eq. 108-16.

torque e corrente
    eq. 108-16

    All these equations make it possible to calculate the induced torque in the engine. When we need to calculate the torque on the shaft of the motor, that is, when the motor is under load, then we must use the eq. 108-17, below.

torque e potencia nominal
    eq. 108-17

    To calculate ωr we must use eq. 108-22, below.


        4.6   Rotor Copper Losses

    The joule losses occur in the copper of the rotor both due to the progressive field and the retrograde field. Losses due to progressive field are given by:

perdas joule progressivas
    eq. 108-19

    Losses due to the retrograde field are given by:

perdas joule retrógradas
    eq. 108-20

    Therefore, the rotor copper losses are given by adding the losses due to the forward and backward field. Then, the losses are:

perdas joule totais
    eq. 108-21

    Here it is important to point out that eq. 108-21 only calculates the copper losses in the rotor due to the progressive and retrograde fields. It does not express the total losses in the motor's copper. To do this, it is necessary to take into account the joule loss in the resistor R1, which can be calculated by PR1 = R1 I12. This loss expresses the power lost in the main winding resistance. So, the total losses in the copper of the motor, which we will represent by Pcu , can be calculated by eq. 108-21a below.

perdas joule totais
    eq. 108-21a

        4.7   Mechanical Power in Single-Phase Motor

    After deducting the losses inherent to the operation of the engine, such as copper losses due to electrical resistance, ventilation and friction losses, and supplementary and core losses, mechanical power represents the energy effectively available to perform work, that is, that power that can be converted from electrical to mechanical form. This power, known as mechanical power can be expressed in several ways. Initially, we will define the relationship between the synchronous angular velocity and the angular velocity of the shaft of the motor, ωr, which are related by the slip , according to eq. 108-22.

relação rotação motor e síncrona
    eq. 108-22

    Thus, making the necessary equivalences we can write the mechanical power as:

 rotação motor e potencia mecanica
    eq. 108-23

    Substituting eq. 108-22 in eq. 108-23, we obtain:

potencia mecanica e rotação síncrona
    eq. 108-24

    Substituting eq. 108-16 in eq. 108-24, we obtain:

potencia mecanica e corrente
    eq. 108-25

    And, based on eq. 108-11 and eq. 108-12, it is also possible to write eq. 108-26, or:

potencia mecanica e potencia progressiva e regressiva
    eq. 108-26

    Simplifying the above expression further, we can also write that

potencia mecanica e potencia no gap
    eq. 108-27

    Note that depending on the data provided in the problem statement, we have several alternatives to calculate the mechanical power.


        4.8   Nominal Power of a Single-Phase Motor

    The rated power of a single-phase induction motor, indicated on the nameplate, is crucial data for users, as it represents the maximum working capacity of the engine under normal operating conditions. This power, expressed in HP (Horse Power), can be converted to the international system of units as watts, using the equivalence that 1 HP is equal to 746 watts. The nominal power, or output power Pnom, is the mechanical energy available on the motor shaft, already discounting all losses inherent to the operation of the motor, including rotating losses. Here, we will symbolize rotating losses due to Prot, which include ventilation losses, friction, in the iron core and, often, losses in the copper. Understanding these parameters is essential for the proper selection of an engine for any specific application, ensuring that the engine can operate efficiently and safely within the requirements of the system in which it will be integrated. This way, it is possible to write the nominal power equation according to eq. 108-28.
potencia nominal ou de saída
    eq. 108-28

       4.9  Input or Electrical Power of a Single-Phase

            Induction Motor

    Note that the electrical power (measured in watts) absorbed from the power supply network by a single-phase induction motor is considered the engine input power and is given by:

potencia de entrada ou elétrica
    eq. 108-29

    In this equation, cos φ represents the power factor of the motor, that is, it is the phase difference between the voltage applied V and the input current I1.

    We must also be aware that the machine's input power must satisfy eq. 108-30.

rendimento do motor monofásico
    eq. 108-30

        4.10   Efficiency in a Single-Phase Motor

    The efficiency, η, of a single-phase induction motor is given by the ratio between the nominal power, that is, the power that the motor available on its axis and the input power, both measured in watts or another equivalent unit. So, we can write:

rendimento do motor monofásico
    eq. 108-31

        4.11   Study of Single-Phase Induction Motor no

             Load and with Locked Rotor

    The study of the equivalent circuit of an induction motor is essential to understand the behavior of the machine under different load conditions. To determine the values ​​of the circuit elements that represent the engine in operation, it is necessary to carry out a series of tests. These include the no load test, which determines the iron losses and magnetization characteristics, and the short-circuit test, which provides information on copper losses and dispersion impedance. Additionally, the locked rotor test can be used to evaluate the rotor resistance and reactance when the motor is stopped. These tests are analogous to carried out on transformers and are essential for accurate modeling of the motor, allowing its performance to be predicted in different operating situations. The analysis of these tests contributes to the optimization of the engine design, improving its efficiency and reliability in practical applications.


        4.11.1   Single-Phase Induction Motor no Load

    When a motor operates at no load, that is, without load, it consumes a minimum electrical current necessary to overcome the internal losses, such as iron losses and friction and ventilation losses. The empty condition is important to determine engine behavior in situations close to ideal operation. During a no-load test, the rated voltage is applied and the electric current is measured by an ammeter connected in series with the motor, as well as the real power consumed, which is indicated by the wattmeter. These measurements allow calculate motor rotational losses, which are crucial for understanding motor efficiency and for designing systems that use electric motors more effectively and economically. Therefore, this test is a valuable tool in electrical engineering to evaluate the performance of motors under controlled conditions.

    Due to the high reluctance in the air gap of an induction motor, the current circulating through the winding of the stator is very high. Thus, the magnetization reactance, Xm, will be much smaller than the resistances that are connected in parallel with this reactance. As a consequence, the factor motor power becomes very low, indicating that most of the current supplied to the motor is out of phase with tension, contributing little to the production of actual work. This delay current, predominantly inductive, causes a significant voltage drop across the inductive components of the circuit.

    Therefore, when the engine is running without load, there are two relevant simplifications to be made. The first is in the case of the progressive rotating field, where the portion R2 / 2 s tends to be a very large value due to the small slip value. So, in this case, eq. 108-33 is valid.

motor a vazio
    eq. 108-33

    The second simplification is in the case of the retrograde rotating field, where the portion X2 / 2 + R2 / 2 (s - 2) is very small when compared to Xm / 2, as shown in eq. 108-34.

motor a vazio
    eq. 108-34

    This allows us to assemble the equivalent circuit for the case of the engine operating empty, as shown a Figure 108-10.

circuito equivalente MI monofásico a vazio
Figure 108-10

    It is observed that a resistance called Rrot was added to the circuit, whose purpose is to represent the rotational losses of the machine. Thus, the power consumed by this resistance represents rotational losses, including losses in the iron-silicon core of the motor stator.

    The current in the rotor due to the progressive flux is very small, so copper losses are neglected. However, the current due to retrograde flow is significant, and the corresponding copper losses are represented by 0.5 R2, as shown in the circuit in Figure 108-10. Therefore, the wattmeter reading corresponds to the powers consumed by R1 + Rrot + 0.5 R2. This series association of resistances can be represented by a single resistance, which we will call empty resistance, whose symbol representative is RNL. See eq. 108-35.

resistencia a vazio
    eq. 108-35

    In the same way as we did for the empty resistance, we will define a empty reactance, as we can deduce from the circuit shown in Figure 108-10. Represented by XNL, this reactance is defined by eq. 108-36.

reatancia a vazio
    eq. 108-36

    And, after defining the no-load resistance and the no-load reactance, we can define the no-load impedance. Representing by ZNL and using the usual definition of impedance, the modulus of this impedance is defined by eq. 108-37.

modulo impedancia a vazio
    eq. 108-37

    And finally, the power read by the wattmeter will be represented by PNL. This power is directly related to the current measured by the ammeter and with RNL, according to eq. 108-38.

potencia a vazio
    eq. 108-38

    Remembering that eq. 108-39 is also valid.

lei de ohm a vazio
    eq. 108-39


        4.11.2   Single-Phase Induction Motor with

                Locked Rotor
    The described method is a standard procedure for testing electric motors for short circuits. The short circuit voltage, VSC, is carefully controlled to be less than the rated voltage, avoiding damage to the engine due to overheating. The current measured by the ammeter during the test should be comparable to the motor's full-load current, providing an indication of winding health and engine efficiency. Furthermore, the blocked rotor condition, where s = 1, simulates a situation maximum load on the engine, allowing the analysis of engine behavior under extreme conditions. This test is crucial to ensuring the safety and reliability of electric motors before they are put into operation or after repairs. With this information it is possible to recreate the equivalent circuit of the engine. See Figure 108-11.
circuito equivalente MI monofásico rotor bloqueado
Figure 108-11

    We must note that since the motor has a blocked rotor and, therefore, s = 1, the resistance R2 / s reduces to R2, which is a very small value. Therefore, as the values ​​of R2 and X2 are small, the motor input current, ISC, will circulate almost entirely through these components, instead of circulating by the magnetization reactance, Xm, which has a much higher value. So, we can say that under these conditions the circuit can be considered as a series of components R1, X1, R2 and X2. Thus, from the circuit shown in Figure 108-11, we easily see that the power, PSC, measured by the wattmeter is given by:

potencia em motor monofásico
    eq. 108-40

    It can be seen that we can calculate the power factor directly, as we know the other variables. This data informs the phase angle between the applied voltage, VSC, and the electric current, ISC. From the circuit, it is also possible to conclude that:

correntes de rotor bloqueado
    eq. 108-41

    Another information that can be removed from the circuit is the electric current, Im, according to eq. 108-42.

correntes de rotor bloqueado
    eq. 108-42

    Where the value of Zm is given by eq. 108-42a.

correntes de rotor bloqueado
    eq. 108-42a

    Now, knowing the value of ISC and Im, we can easily determine the value of Ir using eq. 108-41. And knowing the value of Ir, we can determine the impedance formed through the circuit where the current Ir flows. Calling this impedance Zsec (secondary) we can express it through eq. 108-43 in its Cartesian form.

impedancia rotor bloqueado
    eq. 108-43

    It is important to solve many problems the relationship between the modulus of the impedance and its respective parts real and imaginary. Therefore, we must pay close attention to eq. 108-44.

módulo impedância de rotor bloqueado
    eq. 108-44

    Another important fact that we must highlight is that this method finds the total resistance value, that is, R1 + R2. Then, To find the value of R2 we must know the value of R1. To find the value of R1 we can use the method described in item 4.11.3, below.

    It is worth noting that, in general, it is a consensus to establish a relationship between X1 and X2 of shape quite practical, or X1 = X2.



        4.11.3   Stator Resistance Measurement

    Another widely used method to determine the electrical resistance of the motor magnetization winding, in this case R1, is with the use of a variable DC voltage source and a DC ammeter. The DC source voltage, VDC, is adjusted until the ammeter reads a current, IDC, equal to rated current of the motor. As a result, after some time, the winding will heat up and the measured resistance value will be very close to the real value when the motor is operating at full load (as we know that the electrical resistance of the winding is a function of temperature).

    It is also known that the reactance of the motor is null when subjected to direct current, as well as there will be no voltage induced in the rotor. So, we can determine R1, given that the only quantity that limits the current in the winding is the stator resistance. This value is given by eq. 108-45.

resistencia do estator
    eq. 108-45
    It is important to highlight that this method does not take into account the skin effect, which is a relevant phenomenon in the study of alternating currents, as it directly affects the distribution of electrical current within the conductors. This effect occurs due to the tendency of the current to concentrate in the conductor surface, increasing apparent resistance and, consequently, losses due to the Joule effect. The intensity of this effect is related to the frequency of the alternating current, the magnetic permeability and the electrical conductivity of the conductor material. Because of this, for higher frequencies, the depth current penetration decreases, which justifies the application of a correction factor by manufacturers to the value of resistance calculated for direct current, according to eq. 108-45, in order to obtain a more accurate estimate for alternating current. The mentioned variation from 10% to 20% is a practical measure to compensate for the increase in resistance due to the skin effect, thus ensuring the efficiency and safety of electrical systems. It is essential that engineers and technicians consider this phenomenon when designing and analyzing systems that operate with alternating current, especially at high frequencies.

    5.   Types of Single-Phase Induction Motors

    Single-phase induction motors are widely used in residential and commercial applications due to their relatively low cost and simplicity of design. However, as mentioned, they do not have inherent starting torque. To overcome this, the techniques most common include the use of a starting capacitor, a split-phase auxiliary winding, and a induction motor with permanent capacitor. The starting capacitor provides a phase shift necessary to create a rotating magnetic field, which can start the movement of the rotor. The auxiliary winding, on the other hand, is energized only during starting, providing the necessary torque. The permanent capacitor motor has a capacitor that is connected to the auxiliary winding throughout the operation, improving the engine performance at varying loads. Each of these techniques has its advantages and limitations, and the choice depends on the specific application and torque requirements. Thus, we can summarize the three techniques used in practice.
  • Split phase windings.
  • Windings with capacitors.
  • Shaded stator poles.

    All of these starting techniques are methods in which one of the motor's two rotating magnetic fields is made stronger than the other. In this way, the rotor receives a starting torque in a certain direction.

    We will study each type of engine separately.


        5.1   Split Phase Windings

    The split phase motor is a classic type of induction motor, widely used in applications that do not require a high starting torque. The 90° phase shift between the stator windings is essential to create a magnetic field rotary, which is what allows the engine to operate. The main winding is responsible for continuous operation, while the auxiliary winding, in conjunction with the centrifugal switch, is used only during starting to help overcome the initial moment of inertia. The centrifugal switch is connected in series with the auxiliary winding. The split phase motor is a classic type of induction motor, widely used in applications that do not require a high starting torque. The 90° phase shift between the stator windings is essential to create a magnetic field rotating, allowing the engine to operate. The main winding is responsible for continuous operation, while the auxiliary winding, in conjunction with the centrifugal switch, is used only during starting to help overcome the initial moment of inertia. The centrifugal switch is connected in series with the auxiliary winding.

foto motor com chave centrifuga
Figure 108-12
    In Figure 108-12 we can see an internal image of this type of engine showing the main components, highlighting the position of the centrifugal switch. In Figure 108-13 we can see the simplified equivalent circuit of this type of motor.
esquema motor com chave centrifuga
Figure 108-13

    An important fact in this type of motor is to design an auxiliary winding that has a ratio resistance/reactance higher than in the main winding. To achieve this objective, typically, a thinner gauge wire is used for the auxiliary winding. This is possible because electrical current only flows in the auxiliary winding during starting. This avoids continuous circulation current, which would cause the winding to overheat. Due to the higher ratio of resistance/reactance in auxiliary winding, the electric current in this winding will suffer a small delay in relation to the applied voltage. Already in the main winding this delay will be much greater. As a result, the current in the auxiliary winding will be advance in relation to the current in the main winding. In this way, the auxiliary winding causes one of the opposing rotating magnetic fields of the rotor to be greater than the other, producing a net starting torque for the engine. The phasor plot shown in Figure 108-14 enhances what was stated above.

gráfico de fasor do motor indução monofásico
Figure 108-14

    Split-phase motors have a moderate starting torque with a low starting current. Starting torque can be increased inserting a resistance in series with the auxiliary winding. See Figure 108-15 for the graph showing the behavior of centrifugal wrench on engine torque.

gráfico torque do motor indução monofásico
Figure 108-15

    They are used in applications that do not require very high starting torques, such as fans, blowers and centrifugal pumps. They are available in sizes in the fractional power range and are very inexpensive.

    Important Note

    "The direction of rotation of the motor depends on the spatial angle of the auxiliary winding magnetic field is 90° forward or 90° behind the main winding angle. How can this angle be reversed from 90° forward to 90° backward simply by changing the auxiliary winding connections, then the direction of rotation of the motor can be inverted by changing the auxiliary winding connections, and leaving the main winding connections unchanged."


        5.2   Motors with Starting Capacitor

    The use of a starting capacitor in electric motors is a common practice to improve starting torque, especially in single-phase motors. The capacitor, when connected in series with the auxiliary winding, creates a phase shift between the currents flowing through the motor coils. This results in a field additional rotating magnet that helps the motor start its rotation. The ability to adjust the strength magnetomotive starting current of the auxiliary winding so that it is equal to that of the main winding is crucial as it allows for a more efficient and smooth start. This method is particularly useful in applications that require robust starting torque, such as fans, pumps and some household appliances. However, i t is important to note that the capacitor must be sized correctly for the specific application in order to prevent premature failures and ensure engine operational efficiency.

    See Figure 108-16. Note that, with the insertion of the capacitor in the auxiliary winding, we can control how much the current in the auxiliary winding will be ahead of the current in the main winding. To do this, simply vary the capacitance of the capacitor. Thus, the phase angle of the current in the winding auxiliary current may be such that the current will be in advance of 90° in relation to the current of the main winding. Since the two windings are physically separated of 90°, a phase difference between the currents of 90° will produce a simple uniform rotating magnetic field and the motor will behave exactly as if it were starting with a three-phase power source. In that case, the Motor starting torque may be greater than 300% of its nominal value. Thus, if the phase motor split does not have sufficient starting torque for the application for which it was intended, it may be replaced by a motor with a starting capacitor.

    Typical applications of these motors are in compressors, pumps, air conditioning and other types of equipment whose starts occur with load.

circuito com chave centrifuga
Figure 108-16

    In Figure 108-17 we can see a diagram of the phasors of the currents involved in the torque generation process. This type of motor presents a torque directly proportional to the sine θ, with the angle θ being the angle between the currents Im and Ia. Naturally, maximum torque occurs when θ = 90°. In this configuration, when starting the engine we have I1 = Im + Ia

gráfico correntes
Figure 108-17

    To find an equation that defines the starting torque of this engine we use the equation eq. 108-15 shown below.

torque e potencia
    eq. 108-15

    Let's define the variable a as the turns ratio between the auxiliary winding and the main winding. Considering that in starting s = 1, we can write the following equation for the starting torque (start), τst:

torque de partida
    eq. 108-46

    It is common, in technical literature, to define a new variable by the letter K, in such a way that:

variávle K
    eq. 108-47

    So, the equation eq. 108-46 appears in most technical literature as eq. 108-48below.

variávle K
    eq. 108-48

    In Figure 108-18 we can see the torque graph for this type of engine. Note the significant increase in starting torque when compared to the capacitor less motor torque shown in Figure 108-15.

gráfico torque motor com capacitor de partida
Figura 108-18

        5.3   Motors with Permanent Capacitor

    The starting capacitor does such a good job of improving the torque characteristic versus speed of an induction motor that sometimes the winding auxiliary with a smaller capacitor is left permanently in the motor circuit. If the capacitor value is chosen correctly, this motor will have a perfectly rotating magnetic field uniform for some specific load and it will behave exactly like a three-phase induction motor at that point. This motor is called a permanent capacitor motor or capacitor-run motor. Permanent capacitor motors are simpler than capacitor-start motors, because the starter key is not required. For normal loads, they are more efficient, having a higher power factor and smoother torque than conventional motors ordinary single-phase induction.

    However, permanent capacitor motors have a starting torque lower than capacitor-start motors because the capacitor must be dimensioned with a certain value to be able to balance the winding currents permanent and auxiliary load under normal load conditions. How does the starting current is much greater than the normal charging current, a capacitor that balances the phases with normal loads will leave these phases very unbalanced under operating conditions match. In Figure 108-19 we see a simplified equivalent circuit of this type of motor.

circuito com capacitor permanente
Figure 108-19

    Note that in this configuration the relationship shown in eq. 108-49 is valid for any and all instants of engine operation.

variávle K
    eq. 108-49
    Analysis of the torque graph of a permanent capacitor motor, as shown in Figure 108-20, reveals that the starting torque is not maximized. This can be attributed to several factors, including the motor configuration and capacitor characteristics. Permanent capacitor motors are known for its ability to maintain a constant torque during operation, but starting torque may be limited if the capacitor is not properly sized or if the circuit configuration is not optimized. Furthermore, it is important ensure that the engine is correctly sized for the application in question and that all components are working as expected. Regular maintenance and testing of capacitors can help identify and correct problems that may be affecting engine performance.
torque de partida motor com capacitor permanente
Figure 108-20

        5.4   Motors with Two Capacitors

    Dual capacitor motors are an effective solution for applications that require high starting torque. The use of two capacitors, one for starting and one for continuous operation, allows the motor to develop stronger starting torque and improve efficiency during regular operation. The starting capacitor, with value higher, is crucial during the first moments after activation, as it works to balance the currents between the main and auxiliary windings, resulting in a higher starting torque. Once the engine reaches its rated speed, the centrifugal switch system deactivates the starting capacitor, leaving only the starting capacitor permanently in operation. The latter, being of lower value, generally between 10% to 20% of the starting capacitor, is optimized to maintain current balance under normal load conditions, thus ensuring optimal operation efficient and stable engine. This dual capacitor configuration is particularly useful in equipment that face heavy loads or that need to overcome great initial inertia. See Figure 108-21 for equivalent circuit of this type of engine.

circuito equivalente motor com dois capacitores de partida
Figure 108-21
    Single-phase dual-capacitor motors, which include a starting capacitor, Cst, and a permanent capacitor, CP, offer advantages significant in terms of performance. The starting capacitor provides a substantial increase in starting torque, facilitating starting the engine under load. In Figure 108-22 we can see the graph of the torque developed by the motor with two capacitors. Notice how the starting torque is much higher than that of a motor with a permanent capacitor.
grafico torque motor com dois capacitores de partida
Figure 108-22