A three-phase, star-connected, 1,500 kVA, 60 Hz synchronous generator, operating
at a line terminal voltage of 6,000 V, has an
armature resistance of 0.4 Ω / phase and a synchronous reactance of 6 Ω / fase.
a) calculate the induced voltage for a nominal load with FP = 0.80 lagging;
b) keeping the excitation constant, find the terminal voltage for a nominal load
with FP = 0.80 leading ;
Solution of the Problem 105-8
According to the problem statement, the excitation remains constant, so the induced voltage,
EA, is the one calculated in item a. Let's call the new terminal voltage V'F.
Then, using eq. 105-7.2, we have: