Problem 105-6
Source: Problem created by the website author.
A three-phase 200 kVA synchronous generator, connected in a wye, has an open-circuit line voltage of 2,300 V.
The average DC armature resistance measured between the two lines is R = 0.4 Ω.
When short-circuited, the generator draws a current of 80 A.
Find:
a) the synchronous reactance per phase of the generator;
b) the nominal current of the generator.
Solution of the Problem 105-6
By stating that the line voltage is 2,300 V, then the phase voltage is:
And since we know the short-circuit current, Icc, we can calculate the synchronous impedance per phase. Thus, we have:
The connection is in a star configuration. Therefore, to calculate the phase armature resistance for DC,
we will use eq. 105-23, shown below.
Replacing the variables with their respective numerical values, we find:
Now we can calculate the real value of the armature resistance for AC by applying the correction factor kac.
Using the value of 1.6 (as explained in the theoretical part), we have: