Problem 105-5
Source: Adapted from Example 6.19 - page 559 - SHADEV, S. K. - Book:
Electrical Machines - 1ª Edição - Ed. Cambridge University Press - 2018.
A three-phase synchronous generator connected in a star-type connection has an
armature resistance of 0.1 Ω / phase. When open-circuited, the line voltage is 173.3 V.
When short-circuited, the current is 200 A.
The goal is to maintain a line voltage of 400 V when the generator supplies a load that consumes 100 A.
Find
a) the induced armature voltage, EA, when FP = 0.8 lagging;
b) the induced armature voltage, EA, when FP = 0.75 leading.
Solution of the Problem 105-5
When stating that in open circuit the line voltage is 173.3 V, then the phase voltage is:
And since we know the short-circuit current, Icc, we can calculate the synchronous impedance. Thus, we have: