Problem 105-4
Source: Adapted from Example 6.16 - page 557 - SHADEV, S. K. - Book:
Electrical Machines - 1ª Edição - Ed. Cambridge University Press - 2018.
A single-phase 60 kVA synchronous generator operates at 220 V, 60 Hz, and has negligible armature resistance.
The armature winding reactance is 0.07 Ω.
When the alternator supplies rated current to a load with PF = 0.7 lagging, find:
a) the induced voltage in the armature, EA;
b) the torque angle, δ.
Solution of the Problem 105-4
Based on the data provided by the problem, we will calculate the value of the armature current, Ia.
Knowing that cos φ = 0.7 ⇒ sen φ = 0.714 and remembering that RA ≅ 0,
then it is possible to use eq. 105-07.1, shown below.
Therefore, applying the inverse function of the sine function, we obtain: