Problem 105-3
Source: Adapted from Example 6.3 - page 307 - SEN, P. C. - Book:
Principles of Electric Machines and Power Eletronics - 3ª Edição - Ed. Wilei - 2014.
A three-phase 5 kVA synchronous generator in a wye configuration operates at 208 V, 60 Hz, and has
negligible armature resistance.
The armature winding reactance is 8 Ω / phase.
a)Determine the voltage EMF and the power angle of the generator when it operates at rated power with PF = 0.8 lagging.
b) If the field current is increased by 20%, without changing the prime mover power, find the
armature current, power factor, and reactive power in the machine.
c) With the field current from item a, the prime mover power is increased slowly. What is the
stability limit? What are the corresponding values of the armature current, power factor, and
reactive power for maximum power under this condition.
Solution of the Problem 105-3
Initially, let's calculate the voltage per phase, since the generator is in a star configuration. Thus,
calling it terminal voltage, represented by VT, we have:
Since we know the three phase power and line voltage, the armature current can be calculated using the equation below.
Since the power factor is 0.8, then the lag angle is φ = cos-1 0.8 = - 36.87°.
Therefore, the armature current per phase can be written as: