band brasil
band USA
band espanha







nucleo_trafo95-1J.png
Figure 95-01

nucleo_trafo95-1J.png
Figure 95-02
nucleo_trafo8.png
Figure 95-03
nucleo_trafo4K.png
Figure 95-04

nucleo_trafo5K.png
Figure 95-05

figura trafo trifasico
Figure 95-06
figura corte trafo trifasico
Figure 95-07
figura corte trafo trifasico
Figure 95-08

figura corte nucleo trafo trifasico
Figure 95-09
fator de empilhamento







formula da capitalização

Table 95-01
Manufacturer Price($) Pfe (kW) Pcu (kW) CT ($)
A 30,000 4.00 9.00 38,054.60
B 35,500 3.50 7.00 42,090.85
C 28,450 5.00 11.00 38,387.70
D 28,000 7.00 15.00 43,737.30


sequencia direta
Figure 95-10
sequencia direta
Figure 95-11
sequencia direta
Figure 95-12
sequencia inversa
Figure 95-13
    "At any instant of time, the phasor sum of the three phase voltages of a three-phase generator is NULL."
    The direct and inverse sequences were studied in detail in Chapter 81 and, if the reader is interested in reviewing them, click here     Three-Phase Phasor.

    6.   Connections in a Three-Phase Transformer

    The standard nomenclature of the phases of a three-phase transformer uses the capital letters A, B and C to represent the high voltage winding. The low voltage winding is represented by the lowercase letters a, b and c.

    Each winding has two terminals that receive the subscript 1 and 2.

    The interconnection of the phase windings to generate a three-phase system must meet three possible alternative connection modes: delta connection; star connection and zig-zag connection. Each of these connections has two variations. For example: a star connection can be made by joining the terminals A1, B1 and C1 to form the neutral terminal, leaving A2, B2 and C2 as line terminals. Alternatively, we can join A2, B2, and C2 to form the neutral, and use A1, B1, and C1 as line terminals.

    In Brazil, in distribution transformers, it is common for manufacturers to represent the high voltage terminals with the capital letter H. Thus, we have the terminals H1, H2 and H3. And the low voltage terminals with the capital letter X, being X0, X1, X2 and X3. In this case, the terminal X0 corresponds to the neutral. See Figure 95-14 for a photo of a distribution transformer that illustrates the nomenclature mentioned above.

    According to the standard, the H1 terminal (high voltage) is conventionally positioned to the left of the transformer, when viewed from the low voltage side. Figure 95-14 illustrates this arrangement clearly.

trafo trifásico de distribuição
Figure 95-14

    Since the primary and secondary can be connected in different ways, there are at least twelve possible combinations.

    According to the phase shift that exists between the line voltages on both sides of the transformer, these combinations can be organized into four main groups, as detailed below.

  • Group 1 - phase shift - Notation: Yy0, Dd0 e Dz0.

  • Group 2 - phase shift 180° - Notation: Yy6, Dd6 e Dz6.

  • Group 3 - phase shift 30° lagging - Notation: Yy1, Dd1 e Dz1.

  • Group 4 - phase shift 30° leading - Notation: Yy11, Dd11 e Dz11.

    It is worth noting that this notation is derived from the position of the hand of an analog clock. When the phase shift is , it is understood that the hand is vertically pointing upwards (pointing to the number 12 - taken as a reference - "zero"). When the phase shift is 180°, it is understood that the hand is vertically pointing downwards (pointing to the number 6, 180° from the previous position - 6). And in the case of 30° behind, it is understood that the hand is pointing to the number 1 of the clock (note that the hands of the clock, when considered phasors, rotate counterclockwise). Finally, when there is an advance of 30°, the hand is pointing to the number 11 of the clock.

    Connections in transformers is a broad subject. Therefore, we decided to address this topic in a specific chapter. To access, click here     Connections in Transformers.


    7.   Possible Connections in a Transformer

        Three-Phase

    Most of the power generated and transmitted over long distances in a system is of the three-phase type, this is due to economic reasons. Furthermore, since the third harmonic flux created by each winding is in phase, the preferred winding type is the shell-type , because it provides an external path for this flux. Thus, we can state that the shell-type winding provides a voltage with a less distorted waveform than the core-type winding.

    The primaries and secondaries of any three-phase transformer can be connected independently in so-called star (Y) or delta (Δ) configurations. This means that a three-phase transformer bank can be assembled in a total of four possible connection configurations:

  • 1 -Star - Star(Y – Y)
  • 2 - Delta - Delta (Δ – Δ)
  • 3 -Star - Delta (Y – Δ)
  • 4 - Delta - Star(Δ – Y)

    These configurations have already been studied in chapter 83 - three-phase circuits, which can be revisited in     Three-Phase Circuits.

    For three-phase transformers, the calculations of impedance, voltage regulation, efficiency and other similar calculations are performed taking one phase at a time. For this, the same techniques that have already been developed for single-phase transformers are used.

    Next, we will discuss the advantages and disadvantages of the connection types in three-phase transformers.


        7.1   Conection Star - Star

    Since most transformers are designed to operate at the knee of the magnetization curve, i.e. in the saturation zone, such designs cause the induced currents and the electromotive forces (EMFs) to be distorted. This happens because, although the magnetizing currents are still 120° out of phase with each other, their waveforms are no longer sinusoidal. Thus, if we add the currents, they will be different from zero. Therefore, if the neutral is not grounded, these currents are forced to cancel each other. As a result, they distort the EMF waveform, generating harmonics.

    Thus, three-phase transformers connected in star-star are operated with grounded neutrals, that is, the neutral of the primary is directly connected to that of the power supply. If the neutral remains isolated and an unbalanced load is connected to the secondary, the electrical position of the neutral will shift, altering the magnitudes of the phase voltages. Grounding the neutral on the primary prevents this improper operating condition.

    To illustrate this fact, we will consider the fundamental phasors of the balanced phase voltages. Let us call them e1A, e1B, and e1C, with each phasor having magnitude e1. The third harmonic voltage for each phase is e3. At a given moment, their relative positions are illustrated in Figure 95.10. Since the frequency of the third harmonic of the phase voltage is three times greater than the fundamental, their relative positions vary in time, shifting the position of the neutral N'. This phenomenon is known as swinging neutral. Thus, the maximum voltage in any phase is given by e1 + e3. Figure 95-15 presents a series of illustrations of the oscillating neutral phenomenon.

Deslocamento neutro
Deslocamento neutro
Deslocamento neutro
Deslocamento neutro
Figure 95-15

    Note that the voltage phasors are represented as rotating in the counterclockwise direction. For each 30° rotation, the e3 phasor rotates three times this amount, that is, 90°. Thus, the presence of harmonics in the voltage is undesirable, as it can generate high voltages in the winding insulation. Therefore, the use of a grounded neutral or a tertiary delta winding will allow a path for the third harmonic of the current, thus ensuring a sinusoidal flux and a sinusoidal phase voltage.

    The circuit shown in Figure 95-16 is a star - star configuration for the transformer primary circuit. Note that we have used capital letters to represent the line and phase voltages. Figure 95-17 shows the primary voltage graph. In this configuration, the line voltage leads the phase voltage by 30°, or the phase voltage lags the line voltage by 30°. On the other hand, in terms of magnitude, the line voltage is √3 times the phase voltage.

    In general, we can express the above mathematically using eq. 95-02.

relação entre tensão de linha e fase
    eq.   95-02
    We must also remember that, in a star circuit, the line current is equal to the phase current, according to eq. 95-03.
corrente linha igual corrente fase
    eq.   95-03
Esquema elétrico fases YY
Grafico fases YY
Figure 95-16                       Figure 95-17
Esquema elétrico fases YY
Grafico fases YY
Figure 95-18                       Figure 95-19

    In figures Figure 95-18 and Figure 95-19, we represent the transformer secondary circuit and its respective phasors. In the secondary, lowercase letters are used to represent the phasors. All considerations made for the primary are also valid for the secondary, including equations eq. 95-01 and eq. 95-02. In the study of three-phase transformer connections that will be studied in the next chapter, this configuration is called Yy0 and belongs to group 1. This occurs because the secondary voltage points to the number 12 on the dial of an analog clock. This position is taken as a reference and represented by the number ZERO. Therefore, it is called Yy0.

    The star-star connection is the most economical and has advantages and disadvantages. Let's analyze them.


    Advantages of Star - Star Connection
  • The number of turns per phase and the amount of insulating material are minimal, since the phase voltage is 1 / √3 of the line voltage.

  • There is no phase shift between the primary and secondary voltages.

  • It is possible to connect the neutral, since the star - star configuration provides the neutral points in both windings.


    Disadvantages of Star - Star Connection
  • Under unbalanced load conditions on the secondary side, the load side phase voltages change unless the load neutral point is grounded. This condition is called neutral shift. However, by connecting the primary neutral point to the generator neutral point, the difficulty of neutral shift can be overcome.

  • The transformer primary draws a magnetizing current containing the third and fifth harmonics. If the neutral of the primary winding is not connected to the generator neutral, the third and fifth harmonic currents will distort the central flux and alter the waveform of the output voltages. However, by connecting the primary neutral to the generator neutral, the return path is provided for the third and fifth harmonic currents and thus the problem of voltage distortion is overcome.

  • Even if the primary neutral point is connected to the generator neutral or grounded, the third harmonic may still exist. This will appear on the secondary side. Although secondary line voltages do not contain third harmonic voltages, the 3rd harmonic voltages are additive at the neutral and cause triple frequency neutral current (3rd harmonic) that will cause interference in the nearby communication system.

        7.2   Conection Delta - Delta

    In the following figures, the phase currents in the primary winding are represented by IAB, IBC and ICA while the line currents are represented by IA, IB and IC.

    In the secondary winding, the phase currents are represented by Iba, Icb and Iac, and the line currents are represented by Ia, Ib and Ic.

    Note that the angle φ2 in the figures below represents the load angle. In other words, φ2 represents the load power factor or the phase shift between the transformer's nominal voltage and the phase current. Furthermore, it can be seen that there is no phase difference between the primary and secondary voltages. For this reason, the connection is called Dd0 and belongs to group 1.

Esquema elétrico fases DD
Grafico fases YY
Figure 95-20                       Figure 95-21
Esquema elétrico fases DD
Grafico fases YY
Figure 95-22                       Figure 95-23
    In this configuration, after calculating the phase current, we can find the line current by multiplying the magnitude of the phase current by √3 and subtracting 30° from its angle. Mathematically, this can be expressed using eq. 95-04.
relação entre corrente linha e corrente fase
    eq.   95-04

    In this equation, θF represents the phase current angle, and by subtracting 30° from it, we find the line current angle.

    From the graph in Figure 95-23 and the circuit shown in Figure 95-22, we can write that:

    Ia  =  Iba - Iac
    Ib  =  Icb - Iba
    Ic  =  Iac - Icb

    In this configuration, the components of the third harmonic of the current of the three phases are out of phase with each other by 120°, totaling 360°. Thus, these harmonics are in phase and circulate in the delta winding of the primary. This current produces a sinusoidal flux, resulting in a sinusoidal voltage in the secondary.

    This configuration is used in power systems where large currents and low voltages are used. In addition, this connection is suitable when continuity of service is required, even if one of the phases presents a fault. When operated in this way, the transformer provides three-phase currents and voltages with the correct phase, but its capacity is reduced to 57.7% of the nominal capacity.


    Advantages of Delta - Delta Connection
  • In this configuration, there is no phase shift between the primary and secondary voltages.

  • There is no distortion in the magnetic flux, since the third harmonic components of the magnetizing current flow through the delta connection windings of the primary winding. Thus, the third harmonic does not flow in the line currents.

  • Since the phase current is 1 / √3 times smaller than the line currents, the diameter (or gauge) of the winding conductors is reduced, generating lower costs.

  • This type of connection does not present operational problems, even if the load on the secondary is unbalanced.
    Disadvantages of Delta - Delta Connection
  • The amount of insulating material is greater than in the star - star configuration, since the phase voltage and line voltage are equal.

  • Another problem with this configuration is the absence of a neutral terminal.

        7.3   Conection Star - Delta
    Typically, this configuration is used when it is desired to reduce line voltage, such as at the receiving end of a transmission line. In this connection, the primary's neutral is grounded.
Esquema elétrico fases YY
Grafico fases YY
Figure 95-24                       Figure 95-25
Esquema elétrico fases D
Grafico fases D
Figure 95-26                       Figure 95-27

    As shown in Figure 95-25 and Figure 95-27, it can be seen that the secondary line voltage lags 30° behind the primary line voltage. The same is true for the primary and secondary phase voltages. For this reason, this configuration is called Yd1. In Figure 95-27, it can be seen that the phasor of the voltage Van points to the number 1 on the dial of an analog clock. Hence the name Yd1. This configuration belongs to group 3.

    The third harmonic currents flow within the mesh provided by the delta connection, generating a sinusoidal waveform. Therefore, there are no distortion problems in the output waveform, resulting in a sinusoidal waveform.

    In this configuration, we can establish a relationship between the primary line voltage and the secondary line voltage. Designating V1L for the primary line voltage and V2L for the secondary line voltage, and considering that "a" is the transformer transformation ratio, we obtain eq. 95-05.

relação entre tensão linha e tensão fase
    eq.   95-05

    Advantages of Star - Delta Connection
  • This type of connection does not present problems with third harmonic components, since they are suppressed by a current that circulates in the delta connection of the secondary.

  • This connection is quite stable in relation to unbalanced loads, since the delta connection of the secondary partially redistributes any imbalance that may occur.

  • It is possible to provide a neutral connection on the primary.

  • On the high voltage side of the transformer, the insulation system supports 57.7% of the line voltage. Therefore, there is a reduction in the cost of transformer insulation.

    Disadvantages of Star - Delta Connection
  • Because this connection introduces a phase shift between the secondary voltage and the primary voltage of the transformer, this can cause problems when the secondaries of two transformer banks are placed in parallel.

  • The secondary voltage will lag 30° behind the primary voltage if the phase sequence is direct or ABC. And it will be early if the sequence is reverse or ACB.

        7.4   Conection Delta - Star

    The use of this type of connection allows the neutral of the transformer secondary to be connected to earth. It is quite popular as distribution transformers when it is necessary to reduce the voltage for domestic or commercial use. The grounded neutral contributes to the safety of the distribution system and constitutes a 4-wire system. In this way, this system can supply three-phase equipment, using the three lines (ABC), as well as single-phase systems. Using one of the three available lines and the neutral, we can form a single-phase system. Thus, it is possible to supply single-phase equipment such as fans, lighting, radios, televisions, computers, etc.

    This configuration is also not affected by third harmonics, since the delta connection of the primary suppresses third harmonic currents.

Esquema elétrico fases DD
Grafico fases YY
Figure 95-28                       Figure 95-29
Esquema elétrico fases DD
Grafico fases YY
Figure 95-30                       Figure 95-31

    Comparing the graphs shown in Figure 95-29 and Figure 95-31, we can easily see that the secondary line voltage is 30° ahead of the primary line voltage. In particular, in the graph in Figure 95-31, we can see that the phase voltage phasor, Van, is pointing to the number 11 on the face of an analog clock. Therefore, this configuration is known as Dy11, belonging to group 4.

    On the other hand, it can be seen that the relationship between the line voltage and the phase voltage for the secondary is given by eq. 95-06.

relação entre tensão linha e tensão fase
    eq.   95-06

    Advantages of Delta - StarConnection
  • This type of connection does not present problems with the third harmonic component, since it is suppressed by a current that circulates in the delta connection of the primary.

  • It is a very stable connection in relation to unbalanced loads, since the star connection of the secondary with the grounded neutral ensures operating stability.

  • On the high voltage side of the transformer, the insulation system supports 57.7% of the line voltage. Therefore, there is a saving in the cost of transformer insulation.

    Disadvantages of Delta - Star Connection
  • In this type of connection, the secondary line voltage is √3 times the transformation ratio.

  • The secondary line voltage leads the primary line voltage by 30°.

relação entre delta e zig-zag
Figura 95-32


relação entre tensão linha e tensão fase
Figure 95-33
relação entre tensão linha e tensão fase
relação entre tensão linha e tensão fase

    After these clarifications, we can move on to studying the mathematics of connections.

        8.1   Mathematics of Star-Star Connection
    In the star-star connection, there is no phase shift between the line and phase voltages, as shown in the graphs in Figure 95-17 and Figure 95-19, repeated below for greater understanding.
Grafico fases YY
Grafico fases YY
Figura 95-17                       Figura 95-19
    Thus, in this connection, for the line and phase voltages, the equations studied in item 8 and repeated below are valid.
relação entre tensão linha e tensão fase
    eq.   95-07
    So, naturally, from this equation we can conclude that:
relação entre tensão linha e tensão fase
    eq.   95-08
    It should be noted that in this connection the line and phase currents, both primary and secondary, are iguals. And the primary current and the secondary current are related by the transformation ratio, "a", according to eq. 91-03, studied in Chapter 91 and repeated below.
equa91-3J.jpg
    eq.   91-03

        8.2   Mathematics of Delta - Delta Connection
    In a Delta - Delta connection, the line and phase voltages are the same. Therefore, there is no phase shift between them. The Figure 95-21 and Figure 95-23, repeated below, clearly show this.
Grafico fases DD
Grafico fases DD
Figure 95-21                       Figure 95-23
    Regarding the currents, the graphs show that the line current, both in the primary and secondary, lags 30° behind the phase current. In terms of magnitude, the line current is the phasor sum of two phase currents. Thus, it will be √3 times greater than the phase current (the same case shown in Figure 95-33). If the phase current has an angle θF, then eq. 95-04, studied in item 7.2, is valid.
equa83-15J.jpg
    eq.   95-04
    And the primary current and secondary current, both line and phase, are related by the transformation ratio, "a", according to eq. 91-03, studied in Chapter 91 and repeated below.
equa91-3J.jpg
    eq.   91-03

        8.3   Mathematics of Star-Delta Connection
    In a Star - Delta connection, both the primary and secondary have a line voltage that is 30° ahead of the phase voltage. And the primary phase voltage also leads the secondary phase voltage by 30°. The Figure 95-25 and Figure 95-27, repeated below, clearly show this.
Grafico fases YY
Grafico fases D
Figure 95-25                       Figure 95-27
    Mathematically, the above can be written as eq. 95-13. Note that this phase difference becomes relevant when another transformer is placed in parallel. In this case, attention must be paid to this phase shift.
equa83-1J.jpg
    eq.   95-13
    On the other hand, the Star - Delta connection does not present any problem regarding the sequence zero (component DC and harmonics multiples of 3).

        8.4   Mathematics of Star-Delta Connection
    In the Delta - Star connection, both the primary and secondary line voltage lags the phase voltage by 30°. And the primary phase voltage also lags the secondary phase voltage by 30°. Note that the primary line current also lags the secondary line current by 30°. The Figure 95-29 and Figure 95-31, repeated below, clearly show this.
Grafico fases YY
Grafico fases YY
Figure 95-29                       Figure 95-31
    Mathematically, the above can be written as eq. 95-14. Note that this phase difference becomes relevant when another transformer is placed in parallel. In this case, attention must be paid to this phase shift.
equa95-13J.jpg
    eq.   95-14

        8.5   Mathematics of Zig - Zag Connection
    Our goal is to calculate the secondary phase voltage of the zig-zag connection, as well as the line voltage. These values ​​must be referenced to the primary line voltage by means of the transformation ratio. First, we will calculate the phase voltage based on the diagram shown previously in Figure 95-32. The Figure 95-34 shows a "zoom-in" of the phase voltage, represented by Van. Observing the angle of 30° between the phasors, it is possible to write the value of Van as the sum of the projection of the phasors Vcn and Vca onto it. Since, in terms of magnitude, Vcn = Vca, then let us make Vcn = Vca = VFz, where VFz represents the phase voltage of the zig - zag configuration.
zigzag95-2J.png
Figura 95-34
    Van   =   VFz cos 30° + VFz cos 30°   =   VF (√3/2 + √3/2)
    Performing the calculation, we obtain:
    Van   =   √3 VFz
    eq.   95-15
    Considering the transformation ratio "a" of the transformer, we can find the relationship between the phase voltage of the secondary of the zig - zag connection, represented by Van, and the phase voltage of the primary of the delta circuit, represented by VAN.
    VAN   =   a Van   =   √3 a VFz
    eq.   95-16
    Now let's calculate the relationship between the line voltage of the primary, for example, VAB, and the phase voltage of the secondary of the delta circuit, represented by VAN. We will represent the line voltage of the primary in the delta connection as V. Since in a delta connection we know the relationship between line voltage and phase voltage, given by V = √3 V = √3 VAN, we can write that:
    V   =   3 a VFz
    eq.   95-17
    Considering a = 1, we easily conclude that the line voltage of the delta connection is equal to three times the phase voltage of the zig - zag connection.

    9.   Power in Three-Phase Transformers
    One possible approach to calculating the power in a three-phase transformer is to consider it as a set of three single-phase transformers connected in the appropriate manner. We know that in a single-phase transformer, the apparent power is the product of the applied voltage (VF) and the current (IF) that flows through the transformer winding. Since we have three single-phase transformers, to find the total power, simply multiply the power of each transformer by 3 (three). Thus, we can write eq. 95-18 below.
equa95-15J.png
    eq.   95-18
    Since we know the equation that defines apparent power, we can establish the equations for real or effective power and reactive power. To do this, simply determine the phase shift angle between the voltage and the current, represented by φF. In this way, we arrive at the equations eq. 95-19 and eq. 95-20, presented below.
equa95-18J.png
    eq.   95-19
equa95-19J.png
    eq.   95-20

        9.1   Power in Delta Connection
    Let's analyze a three-phase transformer in delta connection, as shown in Figure 95-35 below.
circ_delta95-1J.png
Figura 95-35
    We know that in this connection the line voltage ( VL = VAB = VBC = VCA ) is equal to the phase voltage ( VF = VAB = VBC = VCA ). And the phase current ( IF = IAB = IBC = ICA ) is √3 smaller than the line current ( IL = IA = IB = IC ). Thus, applying these relations in eq. 95-15, we obtain:
    S  =  3 x VL x IL / √3
    Performing the calculation, we obtain the following eq. 95-21.
equa95-16J.png
    eq.   95-21
    As previously shown, from the apparent power equation, we can determine the real or effective power and the reactive power by using the line voltage and line current. This calculation follows the equations 95-22 and 95-23, presented below. Note that φL represents the phase shift angle between the line voltage and the line current.
equa95-29J.png
    eq.   95-22
equa95-21J.png
    eq.   95-23

        9.2   Power in Star Connection
    Let's analyze a three-phase transformer in Star connection, as shown in Figure 95-36 below.
circ_estrela95-1J.png
Figura 95-36
    We know that in this connection the line current ( IL ) is equal to the phase current ( IF ). And the phase voltage ( VF = VAN = VBN = VCN ) is √3 less than the line voltage ( VL = VAB = VBC = VCA ). Thus, applying these relations in eq. 95-15, we obtain:
    S  =  3 x IL x VL / √3
    Performing the calculation, we obtain eq. 95-21, which is the same equation as the circuit connected in delta.
equa95-16J.png
    eq.   95-21
    Naturally, in this configuration, the equations eq. 95-22 and eq. 95-23 are also valid for calculating the real or effective power and the reactive power.
    Conclusion
    " No matter what the connection configuration, the apparent power of the three-phase transformer is given by eq. 95-21."