band brasil
band USA
band espanha









autotransformador
Figura 94-01
equa91-2J.jpg
equa91-3J.jpg
equa94-4J.png
    However, remember that we are considering negligible losses in the autotransformer. Therefore, we have that I1 N1 = I2 N2. Thus, the above equation can be written as:
    FAB  =  I2 N2 - I1 N2  =  N2 ( I2 - I1 )
    But, using eq. 94-02, we can write:
    FAB  =  N2 ( I2 - I1 )  =  N2 IBC  =  FBC
    Therefore, it is evident that all transforming action (electromagnetic induction) occurs between the windings of section AB and section BC. In other words, the volt-amperes through the winding AB are transferred by means of transforming action to the load that is connected to the winding of section BC, that is, at the terminals designated r-s and shown in Figure 94-01.


        4.1   Transformed Power
    From what was presented in the previous item, we can define transformed power, which we will represent by STR, as that which uses electromagnetic induction as a transforming action, transferring electrical energy from one winding to another. Thus, we can write:
    STR  =  VAB IAB  =  I1 ( V1 - V2 )
    eq.   94-02a
    The total power that will be consumed from the power source and used by the primary in the transformation will be called input power and symbolized by Sin. Thus, we can write Sin = V1 I1. Therefore, we can calculate what portion of the input power is transferred inductively. To do this, let's determine the ratio between the two powers:
    STR / Sin  =  I1 ( V1 - V2 ) / I1 V1  =  1 - ( V2 / V1 )
    Using eq. 91-03 (shown above) and eq. 94-01, we can write:
    STR / Sin  =  1 - ( 1 / a )  =  1 - k
    eq.   94-03
    Thus, we conclude that the portion of the input power (Sin = V1 I1) transferred to the output by inductive action is given by STR = ( V1 - V2 ) I1. Therefore, the extra portion consumed by the load at the output is due to direct conduction, since there is an electrical connection between the primary and secondary. Thus, representing direct conduction by Scon, we have:
    Scon  =  Sin - STR  =  V2 I1
    eq.   94-03a
    And, easily, we conclude that:
    Scon / Sin  =  1 / a  =  k
    eq.   94-04


        4.2   Voltage and Current Relationships

             in an Autotransformer

    To make the equations more objective, we will designate the number of turns of the section AB como:
    NAB = N1 - N2
    Thus, by performing the appropriate algebraic operations, we find the following relations for the autotransformer:
equa94-2J.png
    eq.   94-05
equa94-3J.png
    eq.   94-06


        4.3   Advantage of Autotransformer Regarding

             Apparent Power

    In an autotransformer, part of the power is transferred directly between the primary and secondary, without passing through the windings. This allows it to operate with an apparent power higher than the nominal power of the windings. In other words, it can be more efficient and more economical in certain applications, especially when the voltage difference between the primary and secondary is not very large. To better understand this idea, let us take Figure 94-02 as a reference.
autotransformador elevador
Figura 94-02
    In this item, we will represent the apparent power by the letter S. Thus, for the apparent power of input, we can write:
    S1 = V1 I1
    And for the apparent power of output, we have:
    S2 = V2 I2
    The apparent power is present in the autotransformer windings, that is, the power resulting from electromagnetic induction and is determined by:
    STR  =  ( V2 - V1 ) I2
    So, using the relation STR = V1 ( I1 - I2 ) and relating it to the other equations already developed, we can, after some algebraic manipulation, find the ratio between the apparent input power (or output, since they are the same) and the apparent power that effectively flows through the autotransformer windings. Therefore:
equa94-5J.png
    eq.   94-07

    Therefore, eq. 94-07 describes the nominal apparent power advantage of the autotransformer over the conventional transformer. Note that the smaller the NAB winding, the greater the advantage. This is in agreement with what was mentioned at the beginning of this item, where we stated that it would be more advantageous when the voltage difference between the primary and secondary was not too large.

    Another way to express eq. 94-07 is using the voltages involved in the primary and secondary, according to eq. 94-08.

equa94-6J.png
    eq.   94-08

    Take as an example a 5,000 kVA autotransformer that connects a 110 kV system to a 138 kV system. Using eq. 94-08, we can calculate the nominal apparent power in the windings of this autotransformer.

    STR  =  5.000 ( 138 - 110 ) / 138  =  1.015  kVA

    The autotransformer would have a nominal rating of only 1,015 kVA for the windings, whereas a conventional transformer would have a nominal rating of 5,000 kVA to do the same job. The autotransformer could have a volume up to 5 times smaller than the conventional transformer and would also be much lower in cost, due to the reduced use of copper and iron. For this reason, it is highly advantageous to install autotransformers to connect voltages of similar values.

    It is very important to note that it is usually not possible to simply modify the connections of a common transformer so that it operates as an autotransformer. The reason is that if a common transformer is connected as an autotransformer, the insulation on the low voltage side of the transformer may not be robust enough to withstand the full output voltage. In transformers built especially as autotransformers, the insulation of the smaller coil is as robust as that of the larger coil.


    6.   Advantages of Autotransformer over

        Conventional Transformer


    The autotransformer has several advantages over the transformer. Below, we list some of them.
  • 1 - Since the amount of iron and copper (or aluminum) is smaller, its cost is lower than that of a conventional transformer of similar rating.

  • 2 - It provides more power than a conventional transformer of similar dimensions.

  • 3 - For equal powers, the autotransformer is more efficient than a conventional transformer.

  • 4 - An autotransformer requires a lower excitation current than a conventional transformer to establish the same magnetic flux in the core.

       6.1   Copper Used in Autotransformer and

         Conventional Transformer of the Same Power

    We know that the length of copper required in a winding is directly proportional to the number of turns, and the cross-sectional area of ​​the wire used in the winding is related to the rated current. Thus, the weight of copper required in a conventional transformer with two independent windings is proportional to the total power of the transformer.
    N1 I1  +  N2 I2
    No caso de um autotransformador, o peso de cobre necessário é proporcional a:
    I1 ( N1 - N2 )  +  ( I2 - I1 ) N2
    To find the relationship between the weight of copper required in an autotransformer and in a conventional transformer, which we will call kw, we do:
    kw = ( N1 - N2 )  +  ( I2 - I1 ) N2 / ( N1 I1  +  N2 I2 )
    By manipulating this equation algebraically and remembering that N1 I1  =  N2 I2 , we will find:
    kw = 1 - ( N2 / N1 )  =  1 - ( 1 / a)
    Rearranging the terms, we find eq. 94-10:
equa94-10J.png
    eq.   94-10

    The eq. 94-10 demonstrates that, for example, in an autotransformer with a primary to secondary voltage ratio of 100:33, when applying eq. 94-10, the result obtained is 0.67. This indicates that when using an autotransformer, only 67% of the copper is required compared to what would be required if we were using a conventional transformer with two independent windings. Therefore, the reduction in copper usage is 100% - 67% = 33%.

    On the other hand, by naming the copper savings as Kcu, it can be calculated directly by eq. 94-11 below.

equa94-11J.png
    eq.   94-11
    To better understand, let's analyze an example.
        Example 94-1

    The primary and secondary voltages across an autotransformer are 230 V and 75 V, respectively. Calculate the current in all windings when the load current is 200 A. Also calculate the copper savings.

        Resposta
    To calculate the currents we will use eq. 91-03a, shown below.
equa91-21J.png
    eq.   91-03a

    So, applying the equation, we have:

    I1  =  I2 ( V2 / V1 )  =  200 ( 75 / 230 )  =  65,2   A

    And the current flowing through the common winding is given by I2 - I1, that is:

    I2 - I1  =  200 - 65,2  =  134,8   A

    See Figure 94-07, in which we represent the autotransformer and its currents and voltages.

autotransformador exemplo
Figura 94-07
    As for the copper economy, let's use eq. 94-10. Then, the value of kw, knowing that a = 230 / 75 = 3.066, is:
    kw  =  ( 3,066 - 1 ) / 3,066  =  0,674
    Since the autotransformer uses 67.4% of copper compared to the conventional transformer, the copper savings are:
    Economia de Cu  =  100% - 67,4%  =  32,6%
    Or, using eq. 94-11, we have:
    Kcu  =  1 / 3,066  =  0,326  =  32,6%